(5) Precautions
When using the redundant system in the backup mode, connect the tracking cable to
the control system and the standby system CPU modules.
If both systems are powered on without the tracking cable connected to the CPU
models, the "TRK.CABLE ERR. (error code: 6120)" stop error will occur and the
system cannot run.
If "TRK. CABLE ERR." occurs at power-on, power off System A and System B, then
connect the tracking cable to the CPU modules, and power the systems on again.