5 - 66 
MELSEC-Q
5   DATA USED FOR POSITIONING CONTROL 
 
Da.10
M code (or condition data No./No. of LOOP to LEND repetitions) 
 
Set an "M code", a "condition data No. ", or the "number of LOOP to LEND 
repetitions" depending on how the "
Da.2
Control system" is set. 
 If a method other than "JUMP instruction" and "LOOP" is selected as the 
"
Da.2
Control system" 
............... Set an "M code".   
If no "M code" needs to be output, set "0" (default value). 
 If "JUMP instruction" is selected as the "
Da.2
Control system" 
............... Set the "condition data No." for JUMP. 
0  : Unconditional JUMP to the positioning data specified 
by
Da.9
. 
1 to 10 : JUMP performed according to the condition data No. 
specified (a number between 1 and 10). 
 If "LOOP" is selected as the "
Da.2
Control system" 
............... Set the number of LOOP to LEND repetitions by a number other than 
"0". 
The error "Control system LOOP setting error" (error code: 545) will 
occur if you specify "0".  
 The condition data specifies the condition for the JUMP instruction to be executed.  
(A JUMP will take place when the condition is satisfied.) 
 
[Table 1] 
 
Pr.1
setting value 
Value set with peripheral device 
(unit) 
Value set with sequence program 
(unit) 
0 : mm  0.01 to 20000000.00 (mm/min) 
1 to 2000000000 (
10
-2
mm/min) 
1 : inch  0.001 to 2000000.000 (inch/min) 
1 to 2000000000 (
10
-3
inch/min) 
2 : degree  0.001 to 2000000.000 (degree/min)
1 to 2000000000 (
10
-3
degree/min)
3 : pulse  1 to 1000000 (pulse/s)
 
1 
[QD75P
N/QD75D N] 
1 to 4000000 (pulse/s) 
[QD75P
/QD75D ] 
1 to 1000000 (pulse/s) 
1: In GX Configurator-QP, the QD75P N/QD75D N are recognized as the QD75P /QD75D . Therefore, the 
setting ranges are the same as those of the QD75P
/QD75D . To set a value outside a setting range in GX 
Configurator-QP, set it through a sequence program or GX Works2. The setting ranges in GX Works2 are the 
same as those in sequence programs. (Refer to Appendix 1.2) 
 
[Table 2] 
 
Da.2
setting value 
Setting item 
Value set with peripheral 
device 
Value set with sequence 
program 
JUMP instruction: 82H  Positioning data No.  1 to 600  1 to 600 
Other than JUMP instruction  Dwell time  0 to 65535 (ms)  0 to 65535 (ms) 
 
[Table 3] 
 
Da.2
setting value 
Setting item 
Value set with peripheral 
device 
Value set with sequence 
program 
JUMP instruction: 82H  Condition data No.  0 to 10  0 to 10 
LOOP: 83H  Repetition count  1 to 65535  1 to 65535 
Other than the above  M code  0 to 65535  0 to 65535