5 - 105
MELSEC-Q
5 DATA USED FOR POSITIONING CONTROL
Setting value Default value
Storage buffer
memory address
(common to axes 1
to 4)
Set with a decimal.
Setting
value
K
1
Flash ROM write request
1: Requests write access to flash ROM.
The QD75 resets the value to "0" automatically when the write access completes.
(
This indicates the com
p
letion of write o
p
eration.
)
0 1900
Set with a decimal.
Setting
value
K
Parameter initialization request
1: Requests parameter initialization.
The QD75 resets the value to "0" automatically when the initialization completes.
(
This indicates the com
p
letion of
p
arameter initialization.
)
1
0 1901
Set with a decimal.
Setting
value
K
Deceleration start flag valid
0: Deceleration start flag invalid
1: Deceleration start flag valid
0 1905
Set with a decimal.
Setting
value
K
Stop command processing for deceleration stop selection
0: Deceleration curve re-processing
1: Deceleration curve continuation
0 1907