8 - 18 
MELSEC-Q
8   OPR CONTROL 
 
 Restrictions 
 
A pulse generator with a zero signal is required. 
When using a pulse generator without a zero signal, generate a zero signal using 
an external signal. 
 
 Precautions during operation 
 
(1)  An error "Count method movement amount fault" (error code: 206) will occur 
and the operation will not start if the "
Pr.50
 Setting for the movement 
amount after near-point dog ON" is smaller than the deceleration distance 
from the "
Pr.46
 OPR speed" to "
Pr.47
 Creep speed".  
(2)  If the speed is changed to a speed faster than "
Pr.46
 OPR speed" by the 
speed change function (refer to "12.5.1 Speed change function".) during a 
machine OPR, the distance to decelerate to "
Pr.47
 Creep speed" may not 
be ensured, depending on the setting value of "
Pr.50
 Setting for the 
movement amount after near-point dog ON". In this case, the error "Count 
method movement amount fault" (error code: 206) occurs and the Machine 
OPR is stopped. 
(3)  The following shows the operation when a machine OPR is started while the 
near-point dog is ON.  
 
ON
1)
5)
4)
3)
2)
Zero signal 
Near-point dog OFF 
Pr. 50 Setting for the movement 
amount after near-point dog ON
 
[Operation when a machine OPR is started at 
the near-point dog ON position] 
1)  A machine OPR is started.  
2)  The machine moves at the OPR speed in the 
opposite direction of an OPR.  
3)  Deceleration processing is carried out by 
"
Pr.39
 Stop group 3 sudden stop 
selection" when the near-point dog OFF is 
detected.  
4)  After the machine stops, a machine OPR is 
carried out in the OPR direction.  
5)  The machine OPR is completed after the 
deviation counter clear output is provided on 
detection of the first zero signal after the 
travel of the movement amount set to 
"
Pr.50
 Setting for the movement amount 
after near-point dog ON" on detection of the 
near-point dog signal ON.
 
Fig. 8.13 Count method 1) machine OPR on the near-point dog ON position