10 - 18
MELSEC-Q
10 HIGH-LEVEL POSITIONING CONTROL
The setting requirements and details of the following "condition data"
Da.16
to
Da.19
setting items differ according to the "
Da.15
Condition target" setting.
The following shows the
Da.16
to
Da.19
setting items corresponding to the
"
Da.15
Condition target".
Other setting
item
Da.15
Setting item
Da.16
Condition operator
Da.17
Address
Da.18
Parameter 1
Da.19
Parameter 2
01H: Device X 0 to 1FH (bit No.)
02H: Device Y
07H : DEV=ON
08
H : DEV=OFF
–
0 to 1F
H (bit No.)
–
03H: Buffer memory
(1 word) 1
04H: Buffer memory
(2 words) 1
01
H : =P1
02
H :
P1
03
H :
≤
P1
04
H :
≥
P1
05
H : P1
≤ ≤
P2
06
H :
≤
P1, P2
≤
Buffer
memory
address
P1 (numeric value)
P2 (numeric value)
(Set only when
Da.16
is
[05H] or [06H].)
Low-order 16
bits
Axis 1
positioning
data No. 2
Low-order 16
bits
Axis 3
positioning
data No. 2
05H: Positioning data
No.
10
H : Axis 1 designation
20
H : Axis 2 designation
30
H : Axis 1 and axis 2
designation
40
H : Axis 3 designation
50
H : Axis 1 and axis 3
designation
60
H : Axis 2 and axis 3
designation
70
H : Axis 1, axis 2 and
axis 3 designation
80
H : Axis 4 designation
90
H : Axis 1 and axis 4
designation
A0
H : Axis 2 and axis 4
designation
B0
H : Axis 1, axis 2 and
axis 4 designation
C0
H : Axis 3 and axis 4
designation
D0
H : Axis 1, axis 3 and
axis 4 designation
E0
H : Axis 2, axis 3 and
axis 4 designation
—
High-order 16
bits
Axis 2
positioning
data No. 2
High-order 16
bits
Axis 4
positioning
data No. 2
– : Setting not required (Setting value will be ignored. Use the initial value or a value within the setting range.)
: Value s t o r e d in buffer memory designated in
Da.17
.
1 : Comparison of
≤
and
≥
is judged as signed values. Refer to Section 5.5 "List of condition data" for the setting
contents.
2 : The setting value of start axis (the axis which executes positioning start) should be "0". If the setting value is set
to other than "0", the positioning data set in
Da.18
Parameter 1 and
Da.19
Parameter 2 is given priority to
be executed rather than "
Da.12
Start data No.".