12 - 7 
MELSEC-Q
12   CONTROL SUB FUNCTIONS 
 
[2]   Control Precautions 
(1)  The following table shows whether the OPR retry function may be executed 
by the "
Pr.43
 OPR method".  
 
Pr.43
OPR method 
Execution status of OPR retry function 
Near-point dog  method  :  Execution possible 
Stopper method 1)  :  Execution possible 1 
Stopper method 2)  :  Execution possible 1 
Stopper method 3)  :  Execution not possible 
Count method 1)  :  Execution possible 
Count method 2)  :  Execution possible 
1 Starting can be executed from the position of the limit switch installed in the opposition 
direction of "
Pr.44
 OPR direction". (The limit signal is OFF.) However, the retry 
operation by the limit switch in the OPR direction cannot be executed since a stopper 
is installed in the OPR direction. 
 
(2)  Always establish upper/lower limit switches at the upper/lower limit positions 
of the machine, and connect them to the QD75. If the OPR retry function is 
used without hardware stroke limit switches, the motor will continue rotation 
until a hardware stroke limit signal is detected.   
 
(3)  Do not configure a system so that the drive unit power turns OFF by the 
upper/lower limit switches connected to the QD75. If the drive unit power is 
turned OFF, the OPR retry cannot be carried out. 
 
[3]   Setting method 
To use the "OPR retry function", set the required details in the parameters shown 
in the following table, and write them to the QD75.  
When the parameters are set, the OPR retry function will be added to the 
machine OPR control. The set details are validated at the rising edge (OFF 
 
ON) of the PLC READY signal (Y0). (Set "
Pr.57
 Dwell time during OPR retry" 
according to the user's requirements.) 
 
Setting item 
Setting 
value 
Setting details 
Factory-set 
initial value 
Pr.48
 
OPR retry  1  Set "1: Carry out OPR retry by limit switch".  0 
Pr.57
 
Dwell time during 
OPR retry 
 
Set the deceleration stop time during OPR retry. 
(Random value between 0 and 65535 (ms)) 
0 
 
   Refer to Section 5.2 "List of parameters" for setting details. 
 
REMARK 
•
 Parameters are set for each axis.  
•
 It is recommended that the parameters be set whenever possible with GX 
Configurator-QP. Execution by sequence program uses many sequence programs 
and devices. The execution becomes complicated, and the scan times will 
increase.