8 INSPECTION AND MAINTENANCE
Mitsubishi Diesel Engine S12R OPERATION & MAINTENANCE MANUAL
133
Pub. No. 291Y1-40720 Revision: 5
Fuel System - Check
• When handling fuel, refer to "4 FUEL"
(→ Page 103).
• Devices and equipment outside the
scope of our supply are included in the
facility.
For the details, refer to such a
document as the specification sheet
prepared by the generator supplier.
• For the devices and equipment outside
the scope of our supply, refer to the
corresponding manual of the generator
and the supplier's operation manual.
Fuel Tank - Check and Service
Clean and drain water from the fuel tank.
• The fuel tank is outside the scope of
our supply.
For the details, refer to the
corresponding manual of the generator
and the supplier's operation manual.
â– Fuel Tank - Clean
1 Clean the fuel tank.
2 Refill fuel into the fuel tank, and
bleed the fuel system "
Fuel System -
Bleed Air" (→ Page 134).
Keep away from fire, when working
with flammable substances such as
fuel.
* They may cause a fire.
If fuel leaks or splashes out from the
pipe, do not touch the splashing fuel.
* If the high pressure fuel contacts your skin, it
penetrates your skin and tissues of your skin
may result gangrene.
Wipe off spilled flammable
substances such as fuel thoroughly
with a waste cloth.
* They may cause a fire.
When discarding a waste cloth used
to wipe off combustible material, put
it into a lidded can and obey the
Waste Management and Public
Cleansing Act to handle it as a special
industrial waste.
* It may cause a fire.
* It may cause environmental pollution.
* If you violate rules, you may be subject to
penalties.
Tighten the fuel supply valve to the
engine firmly.
* Otherwise, fuel leaks may cause a fire.
After cleaning the fuel tank, do not
leave the used waste cloth in the fuel
tank.
* Otherwise, it may cause damage to the devices
in the fuel system.
When draining fuel through the drain
cock, always use a container which
can accept all the fuel in the tank.
* Otherwise, the drained fuel will overflow from
the container, which may flow outside of the
facility.
* The fuel drained into the container must be
discarded in accordance with the local laws and
regulations as well as the manufacturer's SDS.