Troubleshooting of Unit does not operate - Table 2
Condition Check Area/Diagnostic
Code
Possible Cause Remedy
Unit does
not operate.
LCD
displays
self-
diagnostic
codes.
FL Drain tank is full of water. 1. Drain the water from the
tank.
2. Place the tank back in the
unit.
3. Press START/STOP
button to start.
Loose drain switch
connection.
1. Reconnect the drain switch
and check connection.
2. Press START/STOP
button to start.
Defective drain switch. 1. Replace the drain switch.
2. Press START/STOP
button to start.