Repair Section
97
11. REASSEMBLY
11.1 Removal of Unit
Reassemble the unit in the reverse order of removal. Described below are the parts that require
special care in reassembling the unit. Perform all wiring or rewiring as referenced in the wiring
diagram.
11.2 Compressor Mounting
Mount the compressor on the frame, using
cushions, steel collars, plate washers and nuts.
11.3 Blower Assembly
Tighten the set screws of indoor and outdoor fans
at the torque shown below.
CAUTION
Tightening torque:
- 10.84 ± 2.17 ft•lbf (15 ± 2.7 N•m)
11.4 Wiring Notice
Secure the wires using clamps so that they do not come into contact with the edges of the
structure. Secure the wires using clamps in the same position they were before removal.