ioLogik E1200 Series Using the Web Console
3-13
Auto Scaling and Slope-intercept functions of the AI value can be defined on this page.
AI Input Range
Set the AI input ranges for each mode, as follows:
1. Voltage Mode (V) (See Jumper Settings (DIO and AI) in Chapter 2 for more details)
There is only one default analog Voltage input range: [0-10V]
2. Current Mode (mA) (See Jumper Settings (DIO and AI) in Chapter 2 for more details)
There are three modes in the analog Current input range: [4-20 mA], [0-20 mA], [4-20 mA (Burn Out)]
NOTE
Only i
nput ranges [0-10 V] and [4-20 mA] support peer-to-peer networking.
AI Input: Current Mode
Burn Out mode indicates when the Current AI has burned out. For example, the 4–20 mA Burn Out mode is
defined in the following diagram: