8 Maintenance and inspection
44 10014218/00 EN
Maintenance
The device does not require maintenance.
Inspection
Depending on the conditions of use of the device and the national regula-
tions in the respective country of use, the transformer manufacturers can
specify different inspection intervals.
Observe the inspection intervals defined in CIGRE Publication No. 445
"Guide for Transformer Maintenance" or the inspection intervals specified
by the transformer manufacturer.
During each transformer inspection, check the following:
1. Check the external condition of the device for contamination, damage
(e.g. broken glass, electrical connection) and corrosion.
2. Vent the device [Section 6.1, Page 35].
3. Check the tightness of the flange connection [Section 5.1, Page 22].
4. Check that the device is functioning correctly [Section 6.3, Page 37].
8.1 Draining the insulation fluid – device version without bypass
If you have to drain insulating fluid from the device for inspection work or
maintenance work on the transformer, proceed as follows:
1. Close the isolation valves to isolate the device.
2. Open the drain valve.
3. Unscrew and remove the drain plugs (wrench size10).
ð The insulating fluid flows out of the device.
4. Capture the insulating fluid in a suitable container.
5. Tighten the drain plugs (wrench size10, 5Nm).
6. Close the drain valve.
7. If necessary, remove the device.
8.2 Draining the insulation fluid – device version with bypass
If you have to drain insulating fluid from the device for inspection work or
maintenance work on the transformer, proceed as follows: