Checking the relay output function is accomplished by proof test every 1 year. And
contact welding shall be check by the proof test.
The relay contacts must be protected with a fuse rated 0.6 of the nominal specified
relay contact current
Special conditions for SIL 3
- The use of the device is allowed only in a 1oo2 - structure.
- The 4-20 mA output of the device must be monitored regarding deviations.