10.3 Checking Wiring and Settings
No COMS on Modbus RTU side. If Tx/Rx are not flashing rapidly then there is a COM issue on the Modbus side. To fix
this problem, check the following:
Visual observations of LEDs on ProtoNode. (Section 10.5 LED Functions)
Check baud rate, parity, data bits, stop bits
Check Modbus device address
Verify wiring
Verify all the Modbus RTU devices were discovered in Web Configurator. (Section 8 Configure the
FieldServer)
No COMS on Modbus TCP/IP side. To fix, check the following:
Visual observations of LEDs on ProtoNode (Section 10.5 LED Functions)
Check device address
Verify wiring
Verify all the Modbus TCP/IP devices were discovered in Web Configurator (Section 8 Configure the
FieldServer)
Field COM problems:
If Ethernet protocols are used, observe Ethernet LEDs on the ProtoNode (Section 10.5 LED Functions)
Visual dipswitch settings (using correct baud rate and device instance)
Verify IP Address setting
Verify wiring
NOTE:If the problem persists, a Diagnostic Capture needs to be taken and sent to support. (Section 10.4
Taking a FieldServer Diagnostic Capture)