Figure 25 Local and Remote Sensors
Table 3 Maximum Mounting Distance for Local and Remote Sensors, Imperial Units
Remote Sensor Local Sensor Max.
Power
1
(W)
Max. Distance (ft)
18 AWG 16 AWG 14 AWG 12 AWG
Passive CB None 6.2 1240 1970 3140 4990
Passive MOS None 11.2 690 1090 1730 2760
Digital CB None 6.2 1240 1970 3130 4980
Digital CB 8.6 890 1420 2260 3590
Digital Toxic 6.9 1110 1770 2810 4460
IR Sensor 11.9 640 1020 1620 2580
Digital Toxic None 3.6 2130 3380 5370 8550
Digital Toxic 4.3 1770 2820 4480 7120
Digital CB 6.7 1140 1810 2880 4580
IR Sensor 9.6 800 1270 2020 3210
IR Sensor None 9.0 850 1350 2140 3410
Digital CB 11.9 640 1020 1620 2580
Digital Toxic 9.7 790 1250 1980 3160
1
- When sizing a system's 24V supply, a 1A inrush current with a 1ms duration should be considered
for each device on the power supply
Assumes transmitter was ordered with relays