Table 4 Maximum Mounting Distance for Local and Remote Sensors, Metric Units
Remote
Sensor
Local Sensor Max.
Power
1
(W)
Max. Distance (m)
1 mm
2
1.5 mm
2
2.5 mm
2
4 mm
2
Passive CB None 6.2 460 690 1150 1840
Passive MOS None 11.2 250 380 630 1010
Digital CB None 6.2 460 690 1150 1840
Digital CB 8.6 330 490 830 1320
Digital Toxic 6.9 410 620 1030 1640
IR Sensor 11.9 240 360 590 950
Digital Toxic None 3.6 790 1180 1970 3150
Digital Toxic 4.3 650 980 1640 2620
Digital CB 6.7 420 630 1050 1690
IR Sensor 9.6 290 440 740 1180
IR Sensor None 9.0 310 470 780 1260
Digital CB 11.9 240 360 590 950
Digital Toxic 9.7 290 440 730 1160
1
- When sizing a system's 24V supply, a 1A inrush current with a 1ms duration should be
considered for each device on the power supply
Assumes transmitter was ordered with relay