MSA S5000 - Table 5 Maximum Mounting Distance for Remote Sensors (Imperial)

MSA S5000
98 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Figure 26 Remote Sensors
Table 5 Maximum Mounting Distance for Remote Sensors, Imperial Units
Remote
Sensor 1
Remote
Sensor 2
Max.
Power
1
(W)
Max. Distance (ft)
18 AWG 16 AWG 14 AWG 12 AWG
IRSensor Digital CB 12.4 620 980 1560 2480
IRSensor Digital Toxic 9.8 780 1240 1980 3150
Digital CB Digital CB 9.1 840 1340 2130 3380
Digital CB Digital Toxic 6.9 1100 1760 2790 4440
Digital Toxic Digital Toxic 4.3 1770 2810 4470 7110
1
- When sizing a system's 24V supply, a 1A inrush current with a 1ms duration should be
considered for each device on the power supply
Assumes transmitter was ordered with relays
29