Table 6 Maximum Mounting Distance for Remote Sensors, Metric Units
Remote
Sensor 1
Remote
Sensor 2
Max.
Power
1
(W)
Max. Distance (m)
1 mm
2
1.5 mm
2
2.5 mm
2
4 mm
2
IRSensor Digital CB 12.4 230 340 570 910
IRSensor Digital Toxic 9.8 290 430 720 1160
Digital CB Digital CB 9.1 310 470 780 1250
Digital CB Digital Toxic 6.9 410 610 1020 1640
Digital Toxic Digital Toxic 4.3 650 980 1640 2620
1
- When sizing a system's 24V supply, a 1A inrush current with a 1ms duration should be
considered for each device on the power supply
Assumes transmitter was ordered with relays
3.6.5 Instructions for Power and Analog Output
WARNING!
Read all electrical warnings and wiring requirements before connecting power to the S5000.
Failure to follow this warning can result in serious personal injury or death.
Connector for HART analog output and power are provided to increase ease of connecting power.
Connect power and remote sensor cable shields to shield terminals on the main PC board. Provide shield terminations inside
he sensor housing as indicated on the installation outline drawing.
1. Remove the cover by turning counter-clockwise.
2. Remove the display module to expose the wiring terminations and sensor connections.
3. Remove the 5.08mm pitch connector for power supply. The power connector is larger than other 3.81mm pitch
connectors.
4. Use a small flat head screw driver to open wire entries on connector.
5. Insert wires to connector so that when installed each wire is in the correct location.
1. +DC
2. -DC
3. mA1 - analog output of sensor1
4. mA2 - analog output of sensor2
6. Tighten screws on connector and tug gently on wires to ensure they are secure.
7. Attach the connector to the board stack.
8. Make sure the appropriate wires are in the correct terminals.
9. Remove enough of the wire housing to expose the 3-4inches of the cable shielding, but do not expose so much that it
goes beyond the cable entry.