TECHNICAL MANUAL
Chapter 9 - User - Control Interface
NGSi 05÷15
27
ENGLISH
EN
The data in this manual are not binding and they can be modified by the manufacturer without notice. Reproduction of this manual is strictly prohibited
Table 3 JOINT OPERATION, RANGE 2
No.
OPERATION ORDER
(A set-point not met)
STATUS OPERATION r10 r15 r12 r16 r23 r24
1
1) Hot water tank
2) After r12 minutes,
heat pump
HEAT /
HEAT+
DOMESTIC
HOT WATER
heat 0/1 0/1/2 set the
minutes
/ 1/3/4/6 0/2
2
1) Hot water tank
2) After r12 minutes,
system backup heater
3) After additional r12
minutes, heat pump
HEAT /
HEAT+
DOMESTIC
HOT WATER
heat 1 0/1/2 set the
minutes
/1/31/3
3
1) Hot water tank
2) After r12 minutes,
heat pump
3) After additional r12
minutes, system backup
heater
HEAT /
HEAT+
DOMESTIC
HOT WATER
heat 1 0/1/2 set the
minutes
/4/61/3
4
1) System backup
heater
2) After r12 minutes,
heat pump
HEAT /
HEAT+
DOMESTIC
HOT WATER
heat 1 0/1/2 set the
minutes
/0/2/51/3
5
1) Hot water tank
2) After additional r15
minutes, heat pump
HEAT+
DOMESTIC
HOT WATER
domestic hot
water
0/1 0/1/2 / set the
minutes
2/3/5/6 0/1
6
1) Hot water tank
2) After r15 minutes,
domestic hot water
backup heater
3) After additional r15
minutes, heat pump
HEAT+
DOMESTIC
HOT WATER
domestic hot
water
0/1 1 / set the
minutes
2/3 2/3
7
1) Hot water tank
2) After r15 minutes,
heat pump
3) After additional r15
minutes, domestic hot
water backup heater
HEAT+
DOMESTIC
HOT WATER
domestic hot
water
0/1 1 / set the
minutes
5/6 2/3
8
1) Domestic hot water
backup heater
2) After r15 minutes,
heat pump
HEAT+
DOMESITC
HOT WATER/
domestic hot
water
0/1 1 / set the
minutes
0/1/4 2/3
9
1) Hot water tank
2) After r12 minutes,
heat pump
HEAT /
HEAT+
DOMESTIC
HOT WATER
both in heat
mode and
domestic hot
water mode
1 1 set the
minutes
set the
minutes
3/6 0
10
1) Hot water tank
2) After r12 minutes,
system/domestic hot
water backup heater
3) After additional r12
minutes, heat pump
HEAT /
HEAT+
DOMESTIC
HOT WATER
both in heat
mode and
domestic hot
water mode
1 1 set the
minutes
set the
minutes
33
11
1) Hot water tank
2) After r12 minutes,
heat pump
3) After additional r12
minutes,
system/domestic hot
water backup heater
HEAT /
HEAT+
DOMESTIC
HOT WATER
both in heat
mode and
domestic hot
water mode
1 1 set the
minutes
set the
minutes
63
12
1) System/domestic hot
water backup heater
2) After r12 minutes,
heat pump
HEAT /
HEAT+
DOMESTIC
HOT WATER
both in heat
mode and
domestic hot
water mode
1 1 set the
minutes
set the
minutes
03