Level Averages
The LEVEL AVERAGES parameter controls the number of tank gauge level reads per-
formed and averaged before the result is displayed on the LCD. This function is useful for
averaging out level variances caused by tank agitation or wave action inside of tanks.
Press the MODE key to change the number of averages to be performed for the selected
tank. The default value is one and up to 20 averages can be selected.
Number of Floats
The number of floats for tank gauge #1 is shown. To change this number press the
MODE key. The choices are one or two floats. The number of floats programmed must
be equal to or less than the number of floats programmed in the DDA tank gauge or
*PROGRAM ERR message will be displayed during measurement mode.
TANK#1 NUMBER OF
FLOATS: TWO
‘Mode’ TO CHANGE
‘Enter’ TO CONTINUE
NOTE:
The system scan rate is directly affected by the level
averaging function. The overall system scan rate is
based on the total of all individual gauge polls. Each
gauge can have a different averaging value. See
appendix C of this manual for additional informa-
tion on calculating system scan rates.
TANK#1 LEVEL AVGS=
1 AVG (1-20)
‘Mode’ TO CHANGE
‘Enter’ TO CONTINUE
NOTE:
The selected level resolution will directly affect the
tank gauge (sensor) scan rate. The higher the resolu-
tion selected, the slower the overall system scan rate
will be. See appendix C of this manual for additional
information on calculating system scan rates.
TANK#1 RESOLUTION:
0.001 in
‘Mode’ TO CHANGE
‘Enter’ TO CONTINUE
46