Analog I/O Unit
FP0
4-15
Matsushita Automation Controls
4.5 Wiring
D
For voltage output
Value of WY K-2000 K0 K2000
Digital value to DA converter
0 2047 4095
Analog output
-10 V 0V +10 V
D
For current output
Value of WY K0 K2000 K4000
Digital value to DA converter
0 2047 4095
Analog output
0mA 10 mA 20 mA