W415-3101 / B / 01.09.23
15
IOM
7.2 ACCEPTABLE MATERIALS IN UNITED STATES
7.0 VENTING AND COMBUSTION PIPING
7.1 ACCEPTABLE MATERIALS IN CANADA
H3.10
READ, UNDERSTAND AND FOLLOW ALL INSTRUCTIONS IN THIS SECTION. FAILURE TO
PROPERLY VENT OR SUPPLY COMBUSTION AIR TO THIS FURNACE CAN CAUSE CAR-
BON MONOXIDE POISONING, OR AN EXPLOSION OR FIRE, RESULTING IN PROPERTY
DAMAGE, PERSONAL INJURY OR LOSS OF LIFE.
WARNING
!
!
H11.2
E ective August 1, 2007, all vent piping materials and ttings for ue gas venting must be ULC S636 listed
and identi ed as such on the material. The rst 3ft. (900mm) of venting must be readily available for visual
inspection. Speci ed primers and glues of the certi ed vent system must be from a single system manufacture,
and not intermixed with other system manufacture’s vent system parts. The components of the certi ed vent
system must not be interchanged with other vent systems, or unlisted pipe, and or ttings. Follow the venting
manufacturers instructions on installation, cutting, de-burring, cementing, curing and supporting of the venting
system.
Furnace must be vented with ULC S636 certi ed PVC manufactured by IPEX, and Royal Building Products
(GVS-65 & GVS90), or ULC S636 certi ed PPE manufactured by M&G Duravent.
PVC vent terminations may use concentric kits listed in section 10.3 - or terminate using 45 and 90 degree
elbows, or a tee.
PPE venting must terminate using 45 and 90 degree elbows.
Minimum rating of 149 degrees F (65°C).
H11.2B
Furnace venting may be comprised of:
Schedule 40 PVC, ASTM D1785 or CSA B137.3
PVC-DWV, ASTM D2665 or CSA B181.2
Schedule 40 CPVC, ASTM F441 or CSA B137.6
PVC PRIMER AND SOLVENT CEMENT: ASTM D2564
PPE ULC S636 Manufactured by M&G Duravent - must terminate using 45 and 90 degree elbows, or
a tee.
Follow piping manufacturers instructions on proper installation of piping and ttings including cutting, deburring
,
priming, cementing, curing and supporting.
NO ‘B’ VENT APPLICATIONS ALLOWED.