Model Vin +/- 15% [VAC] Max V out [VAC] Max I in [A] Max I out
[A]
Typical motor
P2 [kW]
Maximum
efficiency [%]
Size
3 x Vin 11 3
V218 1 x 230 3 x Vin 38 18 4 95 2
V225 1 x 230 3 x Vin 53 25 5,5 95 2
V306 3 x 230 3 x Vin 5,4 6 1,1 97 1
V309 3 x 230 3 x Vin 8 9 2,2 97 1
V314 3 x 230 3 x Vin 13,5 14 3 97 2
V318 3 x 230 3 x Vin 17,5 18 4 97 2
V325 3 x 230 3 x Vin 24 25 5,5 97 2
V330 3 x 230 3 x Vin 29 30 7,5 97 2
V338 3 x 230 3 x Vin 42 38 9,2 98 3
V348 3 x 230 3 x Vin 52 48 11 98 3
V365 3 x 230 3 x Vin 68 65 15 98 3
V375 3 x 230 3 x Vin 78 75 18,5 98 3
V385 3 x 230 3 x Vin 88 85 22 98 3
V3118 3 x 230 3 x Vin 120 118 30 98 3
V3158 3 x 230 3 x Vin 160 158 37 98 4
V3185 3 x 230 3 x Vin 190 185 45 98 4
V3215 3 x 230 3 x Vin 220 215 55 98 4
V3268 3 x 230 3 x Vin 270 268 75 98 4
V406 3 x 380 - 460 3 x Vin 5,4 6 2,2 97 1
V409 3 x 380 - 460 3 x Vin 8 9 4 97 1
V414 3 x 380 - 460 3 x Vin 13,5 14 5,5 97 2
V418 3 x 380 - 460 3 x Vin 17,5 18 7,5 97 2
V425 3 x 380 - 460 3 x Vin 24 25 11 97 2
V430 3 x 380 - 460 3 x Vin 29 30 15 97 2
V438 3 x 380 - 460 3 x Vin 42 38 18,5 98 3
V448 3 x 380 - 460 3 x Vin 52 48 22 98 3
V465 3 x 380 - 460 3 x Vin 68 65 30 98 3
V475 3 x 380 - 460 3 x Vin 78 75 37 98 3
V485 3 x 380 - 460 3 x Vin 88 85 45 98 3
V4118 3 x 380 - 460 3 x Vin 120 118 55 98 3
V4158 3 x 380 - 460 3 x Vin 160 158 75 98 4
V4185 3 x 380 - 460 3 x Vin 190 185 90 98 4
V4215 3 x 380 - 460 3 x Vin 220 215 110 98 4
V4268 3 x 380 - 460 3 x Vin 270 268 132 98 4
General electrical specifications:
Power supply frequency 50 - 60 Hz (+/- 2%)
Voltage unbalance between the power supply phases +/- 2%
Maximum output frequency 300 Hz
EMC compliance EN61800-3 C2
Energy efficiency class (according to EN61800-9-2) IE2
Environmental specifications:
Relative humidity of the operating environment 5 - 95 % non-condensing
Workplace temperature from -10 °C (14 °F) to 60 °C (140 °F)
Maximum workplace temperature at nominal load 40°C (104 °F)
Power derating beyond maximum temperature -2.5% every °C (-1.4% every °F)
Maximum altitude at nominal load 1000 m (3280 ft)
Power derating beyond maximum altitude - 1% every 100 m (328 ft)
Mechanical specifications: