5-10 | ni.com
Chapter 5 Analog Output
AO Sample Clock Timebase Signal
The AO Sample Clock Timebase (ao/SampleClockTimebase) signal is divided down to provide
a source for AO Sample Clock.
You can route any of the following signals to be the AO Sample Clock Timebase signal:
• 100 MHz Timebase (default)
•20MHzTimebase
• 100 kHz Timebase
•PXI_CLK10
• PFI <0..15>
• RTSI <0..7>
• PXI_STAR
• PXIe_DSTAR<A,B>
• Analog Comparison Event (an analog trigger)
AO Sample Clock Timebase is not available as an output on the I/O connector.
You can use an external sample clock signal as AO Sample Clock Timebase signal
by dividing the signal down in a DAQ device. You can also use it as AO Sample Clock
signal without dividing the signal.