PowerRouter • Solar Inverter • Installation manual 7 Troubleshoot
37
EN
G028-H Hard An error occurred on one of the
internal voltage supplies of the
grid module (G)
Restart the system (section 7.6.1)
The system should recover from the error after the
restart
Contact your dealer if this error occurs frequently
G029-S Soft The grid module (G) start-up
procedure failed
After one minute the error will disappear and normal
operation will resume
Contact your dealer if this error occurs frequently
G031-H Hard There was an overpower on the
output of the PowerRouter
Turn off the loads connected to the PowerRouter
Restart the system (section 7.6.1)
G034-H Hard See P092-H
G036-H Hard See P098-H
G039-S Soft The output power of the grid
module (G) has been reduced
because the grid frequency was
too high
The error will disappear and normal operation will
resume when the grid frequency is within approved
limits
G040-S Soft The output power of the grid
module (G) has been reduced
because the grid voltage was too
high
The error will disappear and normal operation will
resume when the grid voltage is within approved
limits
G041-S Soft The output power of the grid
module (G) has been reduced
because the 10 minute average of
the grid voltage was too high
The error will disappear and normal operation will
resume when the 10 minute average of the grid
voltage is within approved limits
G043-H Hard Error occured in anti-islanding
settings.
Restart the system (section 7.6.1)
Run the installation wizard or tool again and select
country.
S002-S
S023-S
Soft The internal temperature of the
solar module (S) is too high
The output power of the module
has been reduced
Check the airflow of the PowerRouter (section 7.6.2)
When the module cools down the error will
disappear and the normal operation will resume
Contact your dealer if this error occurs frequently
S004-S Soft The solar string voltage
connected to one or both of the
inputs exceeds 600 volts
Check the solar panel configuration and wiring
The error will disappear when the voltage on both
strings drops below 600 volts
S005-S Soft An overvoltage occurred on an
internal bus of the solar module
(S)
The error will disappear when the voltage drops
below the limit
Contact your dealer if this error occurs frequently
S007-S Soft An overcurrent occurred on an
internal circuit of the solar module
(S)
After ten minutes the error will disappear and
normal operation will resume
Contact your dealer if this error occurs frequently
S013-S Soft The output power of the solar
panels exceeds 6000 watts
This error will disappear when the power drops
below 6000 watts
Contact your dealer if this error occurs frequently
S016-S Soft There was an internal
communication error within the
PowerRouter
The error will disappear automatically and normal
operation will resume
C
ontact your dealer if this error occurs frequently
S019-H Hard See P092-H
S021-H Hard See P098-H
S024-S Soft Problem with the onboard supply
voltage, or the SOlar boost limiter
is activated.
The system will recover automatically.
Contact your dealer if this error occurs frequently

Table of Contents

Other manuals for Nedap PowerRouter

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Nedap PowerRouter and is the answer not in the manual?

Nedap PowerRouter Specifications

General IconGeneral
BrandNedap
ModelPowerRouter
CategoryInverter
LanguageEnglish

Related product manuals