EasyManua.ls Logo

Neets 2:25 - RS-232 Configuration; RS-232 Port Parameter Setup; RS-232 Data Transmission

Neets 2:25
28 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 27 of 28
RS-232 settings
The RS-232 settings commands are used to congure the RS-232 interfaces on the amplier.
Please remember to store the settings with the Save command if you want the unit to remember
the settings after a reboot.
All commands start with: NEUNIT=<A>,SETTINGS=RS-232 , RS-232 =<B>,
Where <A> is the unit ID, default 1 and <B> is the RS-232 number to control. All commands
must end with a \CR.
Description: Syntax <X> Default <X> R/W
Set the comport baud rate BAUDRATE=<X> 1200,2400,4800,
9600,14400,19200,
38400,57600,115200
0 R/W
Set the comport data bit DATABIT=<X> TRUE or FALSE FALSE R/W
Set the comport parity PARITY=<X> ON OR OFF OFF R/W
Set the comport stop bit STOPBIT=<X> -70 to -30 -50 R/W
Set the comport TCP Port
number (if used as LAN
gateway)
IPPORT=<X> -70 to -30 -50 R/W
Example of use:
- NEUNIT=1,SETTINGS=RS-232 ,RS-232 =1,BAUDRATE=19200,DATABIT=7\CR <- Sets
RS-232 port 1 to 19200 baud rate and 7 databit.
- NEUNIT=1,SETTINGS=RS-232 ,RS-232 =2,IPPORT=3570\CR <- Sets RS-232 port 2
IP port to 3570.
RS-232 control
The command below sends out a command on the RS-232 port.
For all commands the mandatory start sequence look like this: NEUNIT=<A>,RS-232 =<B>
Where <A> as default is 1, and <B> is the RS-232 port number to use. All commands must be
started with a “,” and all lines must end with a \CR
Description: Syntax <X> Default <X> R/W
Data container.
Each byte must be converted to
a 2 byte ASCII value.
Fx: “Neets” becomes
“4E65657473”
DATA=<X> Up to 500
bytes of date
R/W
Example of use: NEUNIT=1,RS-232 =2,DATA=4E65657473\CR - Sends “Neets” on RS-232
port 2

Related product manuals