LONG RADIO MESSAGE
Setting this option ON enables Long Radio Message for Radio Keys and Radio
Devices. Radio detectors will now need the encryption link turned on. Enabling Long
Radio Message gives greater protection against coding clashes with third party radio
signals.
PROGRAMMING SEQUENCE:
P68E 3E toggles the option ON and OFF
OFF: Normal Radio Message
ON: Long Radio Message
P68E 3E
Available in D8x/D16x V5.6 and later.
PROGRAM MODE LEVEL
Installer mode or NessComms.
FACTORY DEFAULT
ON: Long Radio Message.
NOTE
Older detectors and radio keys without
encryption will not work with this setting on.
DOUBLE PRESS RADIO PANIC
Setting this option ON enables Double Press Panic for Ness Radio Keys, if fitted. The
panel will look for two radio Panic signals in a row to sound the Panic alarm.
OPERATION. On the Radio Key, press and hold Panic until the transmit LED turns on.
Wait until the LED turns off then release the Panic button and immediately press and
hold again until the transmit LED turns on a second time.
This requirement meets regulations in some states of Australia.
PROGRAMMING SEQUENCE:
P68E 1E toggles the option ON and OFF
OFF: Single Press Radio Panic
ON: Double Press Radio Panic
P68E 1E
Available in D8x/D16x V6 and later.
PROGRAM MODE LEVEL
Installer mode or NessComms.
FACTORY DEFAULT
OFF: Single Press Radio Panic.
AUTO RE-ARM
Auto Re-Arm checks that you have entered the premises after disarming.
After disarming, the panel will wait for the same time set for Entry Delay. If all zones
remain sealed the panel will re-arm. This is most useful when used with radio keys
where the OFF button might be accidentally pressed after you have armed and are
leaving the premises.
PROGRAMMING SEQUENCE:
P68E 2E toggles the option ON and OFF
OFF: Auto Re-Arm disabled
ON: Auto Re-Arm enabled
P68E 2E
Available in D8x/D16x V6 and later.
PROGRAM MODE LEVEL
Installer mode or NessComms.
FACTORY DEFAULT
OFF: Auto Re-Arm disabled.
NOTES

the panel is disarmed during the exit
delay time. This allows you to disarm
immediately if you change your mind
about leaving the premises.

on both Areas 1 and 2.
RELATED OPTIONS


For example, say P26E is 30sec, if you
disarm the panel and do not enter the
premises, then the panel will Auto Re-arm in
30 seconds.
Option No. Description Default
P68E
1E Double Press Radio Panic
OFF
2E Auto Re-Arm
OFF
3E Long Radio Message
ON
4E 
OFF
5E 
OFF
6E 24hr Zone Fire Siren sound
OFF
7E Single Shot strobe on Arm by R/Key
OFF
8E Quiet chirps on radio Arm/Disarm
OFF
34
NESS D8X / D16X DELUXE CONTROL PANEL – INSTALLATION MANUAL