II. 3. 6. Modem configuration (menu 6)
The modem configuration menu enable the NetMan to communicate with a modem.
The modem will be connected to the Terminal port.
There are 2 telephone numbers that can be called in the sequence: number 1- number 2, for the
numbers of repeat configured and waiting the delay time configured.
The modem init string is used to configure the modem, the default init string for US Robotics
modem is:
ATE0V1&H0&R1&I0&D0S0=0&W
The alarm level define for what alarm the NetMan will start to call:
0 no call
2 call for internal fault alarm
3 call for all alarm.
The accept incoming call flag enable/disable the possibility that an external modem call . This
may be used for security reasons.