II. 5 Testing and verifying the installation
HTTP
Open the browser and write the NetMan IP address on the location you must see the UPS
status.
UDP
Start the upsview giving the NetMan IP address, you must see the UPS status with all the
values not in the form "???"
SNMP
Verification of the basic physical address of Network Adapter:
From the NMS, perform Ping on the IP address assigned to Network Adapter.
SNMP Get :
From the NMS, perform SNMP Get from MIB OID controller.
SNMP Set :
From the NMS, perform SNMP Set on MIB OID controller.
SNMP Trap:
From Network Adapter, emulate Trap to the NMS. One of the ways how to do it is to
simulate a drop-out.