PREPARATION Part Number 12762 Rev 1.1 | April 30, 2014
Included in this Package
| NETWORK CONTROLLER 3E & 6E MOUNTING AND WIRING GUIDE 5
Preparation
Unpack the controller and inspect the package contents for damaged or missing
components. If damaged, notify the appropriate carrier at once and return any
damaged components for immediate repair or replacement. See “Returning a
Defective Unit” on page 31.
• Included in this Package
• Material and Tools Required
Included in this Package
Included in this package you should find the following items:
• A JACE-3E or JACE-6E controller.
•This
Network Controller 3E & 6E Mounting and Wiring Guide
,
Part Number 12762 Rev 1.1.
• a hardware bag containing the following items:
— One (1) grounding wire, with quick-disconnect 0.187" female connector.
Material and Tools Required
The following supplies and tools are typically required for installation:
• A suitable power module, as one of the following types:
— NPB-PWR: 24Vac or 24Vdc, in-line, DIN mount capable, with grounding wire.
— NPB-PWR-UN: 120–240Vac, in-line, DIN mount capable, with grounding wire
—WPM-XXX: External wall-mount power adapter (input 90–254Vac, 50–60 Hz,
output: 15Vdc, 1A), where XXX varies by AC wall plug, for installation locale,
as: WPM-US (U.S. or Japan installations), WPM-EUR (European installations,
type “C” plug), or WPM-UK (United Kingdom installations, type “B” plug).
Note Using an NPB-PWR power module provides the widest operating
temperature range. See “Environmental Requirements,” page 8.
• If using a NPB-PWR (24V) power module, either one of the following:
— UL listed, Class 2, 24Vac transformer, rated at minimum of 7.5VA to 20VA
(approximate range of controller alone, to fully-expanded unit with four addi-
tional T-IO-16 modules and other option boards). Note that a dedicated trans-
former is required (cannot also power additional equipment).
— 24Vdc power supply, capable of supplying at least 1A (24W).
• DIN rail, type NS35/7.5 (35mm x 7.5mm) and DIN rail end-clips (stop clips), rec-
ommended for any installation that includes NPB-PWR or NPB-PWR-UN power
module and/or optional I/O modules.
• Suitable tools and fasteners for mounting unit and accessories.
• #2 phillips screwdriver: used to install and remove any option card.
• Small flat-blade screwdriver: used for making wiring connections to removable
screw terminal plugs, also for mounting and removing modules from DIN rail.