EasyManuals Logo
Home>Nibe>Heat Pump>F1245

Nibe F1245 Service Manual

Nibe F1245
80 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #17 background imageLoading...
Page #17 background image
Brine side
1x230 V
12 kW10 kW8 kW5 kW
3BarMax system pressure
0.470.400.330.19l/sMin flow
0.650.510.420.23l/sNominal flow
69854862kPaMax external available pressure at nom flow
See diagram page 76.°CMax/min incoming temperature
-12°CMin outgoing temperature
3x230 V
12 kW10 kW8 kW6 kW
3BarMax system pressure
0.470.400.330.25l/sMin flow
0.650.510.420.30l/sNominal flow
69854858kPaMax external available pressure at nom flow
See diagram page 76.°CMax/min incoming temperature
-12°CMin outgoing temperature
3x400 V
12 kW10 kW8 kW6 kW5 kW
3BarMax system pressure
0.470.400.330.250.19l/sMin flow
0.650.510.420.300.23l/sNominal flow
6985485862kPaMax external available pressure at nom flow
See diagram page 76.°CMax/min incoming temperature
-12°CMin outgoing temperature
17Chapter 3 | System descriptionF1245