Information messages
In the event of an information message, the green light
lights up on the front, and a symbol with a service tech-
nician is displayed in the information window, until the
message is reset. All information messages are automat-
ically reset, if the cause is rectified. These messages are
not registered in the alarm log.
May be due toHeat pump action.CauseInformation in
display
No.
The sensor and its connec-
tions
Only informationSensor temporarily missingSensor fault: BT7
HW sensor top
107
The sensor and its connec-
tions
Only informationSensor temporarily missingSensor fault:
BT10brine in
110
The sensor and its connec-
tions
Only informationSensor temporarily missingSensor fault
BT23
123
The sensor and its connec-
tions
Only informationSensor temporarily missingSensor fault
EP23-BT2
138
The sensor and its connec-
tions
Only informationSensor temporarily missingSensor fault
EQ1-BT64
139
Phase fuse
Cable connections
Only informationCompressor phase 1 has been
briefly missing.
Compressor
phase 1 missing
140
Phase fuse
Cable connections
Only informationCompressor phase 2 has been
briefly missing.
Compressor
phase 2 missing
141
Phase fuse
Cable connections
Compressor phase 3 has been
briefly missing.
Compressor
phase 3 missing
142
Communication cables.Temporary problem with the
communication from the base
card to the motor protection
Temporary gen-
eral phase fault
145
No action necessaryHigh pressure switch has
tripped once
Temporary HP
alarm
150
The sensor and its connec-
tions
Only informationSensor temporarily missingSensor fault
CL11-BT51
151
- Contact an authorised refriger-
ation technician
The compressor is stoppedThe hot gas (BT14) has been
temporarily above 135 °C
Hot gas alarm155
SettingsResets automatically when the
temp has fallen 1 °C
BT11 < Minimum value of
brine out
Low temp brine
out
160
SettingsBrine in has reached set max
temperature.
High HTFin161
SettingsCondenser out has reached
max permitted temperature
High condenser
out
162
SettingsResets automatically when
condenser in has fallen two
degrees
Condenser out has reached
max permitted temperature
High condenser
out temperature
162
SettingsResets automatically when
condenser in has fallen two
degrees
Condenser in has reached max
permitted temperature
High condenser
in temperature
163
33Chapter 6 | TroubleshootingF1245

Other manuals for Nibe F1245

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Nibe F1245 and is the answer not in the manual?

Nibe F1245 Specifications

General IconGeneral
RefrigerantR410A
Control SystemNIBE SMO 40
Dimensions (HxWxD)1800 x 600 x 620 mm
Energy Efficiency Class Heating 35°CA++
Energy Efficiency Class Heating 55°CA++
Heating Capacity5-12 kW
COP Heating4.5
Integrated Hot Water Tank180 liters
Power Input Heating1.0 - 3.0 kW

Related product manuals