May be due toHeat pump action.CauseInformation in
display
No.
Exhaust air temperature has
reached permitted min tem-
perature
Low exhaust air
temperature
164
Fault in the electrical anodeElectrical anode
incorrect
166
Communication cables and
connections
Only informationCommunication with the in-
put card is temporarily miss-
ing.
Com. error input
card
170
Communication cables and
connections
Only informationCommunication with the base
card is temporarily missing.
Com. error base
card
171
Communication cables and
connections
Only informationCommunication with the soft-
start card is temporarily miss-
ing.
Com. error soft-
start card
172
Communication cables and
connections
Only informationCommunication with access-
ory card for climate system 2
temporarily missing
Com. error heat-
ing system2
173
Communication cables and
connections
Only informationCommunication with access-
ory card for climate system 3
temporarily missing
Com. error heat-
ing system3
174
Communication cables and
connections
Only informationThe soft-start board is started
up. Takes approx. 20 seconds.
Start-up of soft-
start card
175
Communication cables and
connections
Only informationCommunication with access-
ory card for climate system 4
temporarily missing
Com. error heat-
ing system4
176
Communication cables and
connections
Only informationCommunication with access-
ory card for mixing valve con-
trolled additional heat tempor-
arily missing
Com. error addi-
tion with mixing
valve
177
Communication cables and
connections
Only informationCommunication with access-
ory card for pool temporarily
missing
Com. error pool178
Communication cables and
connections
Only informationCommunication with the ac-
cessory FLM is temporarily
missing.
Com. fault FLM179
Operating settingsPermits room heatingAnti-freeze active. Occurs if
the outdoor temperature is
below 3 °C and no heating is
permitted
Freeze prot180
Operating settingsOnly informationPeriodic increase did not reach
the stop temperature in five
hours.
Unsuccessful
periodic in-
crease
181
F1245Chapter 6 | Troubleshooting34

Other manuals for Nibe F1245

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Nibe F1245 and is the answer not in the manual?

Nibe F1245 Specifications

General IconGeneral
RefrigerantR410A
Control SystemNIBE SMO 40
Dimensions (HxWxD)1800 x 600 x 620 mm
Energy Efficiency Class Heating 35°CA++
Energy Efficiency Class Heating 55°CA++
Heating Capacity5-12 kW
COP Heating4.5
Integrated Hot Water Tank180 liters
Power Input Heating1.0 - 3.0 kW

Related product manuals