62 NIBE F1330
Control
Menu 6.3.4 Shuntintensification [U]
Here you select how many seconds the shunt (SV-P) shall
run in relation to the difference between the calculated
flow and the true flow. For example, a difference of 2
degrees and a set amplification of 5 gives 10 seconds in
control of the shunt. The value is adjustable between 1 and
10. The factory setting is 1.
Menu 6.3.5 Timefactor oilboiler [U]
The time factor of the oil boiler since first start up is shown
here. The value is saved in the microprocessor and thus is
not reset even when boiler is switched off using the main
power switch.
Menu 6.3.6 Return [U]
Pressing the enter button returns you to menu 6.3.0.
Menu 6.4.0 HPAC/PKM settings [U]
Pressing the enter button takes you to sub-menus for
the HPAC-settings. Only shown when HPAC is selected in
menu 9.1.10.
Menu 6.4.1 Cooling [U]
Here is cooling function can be set On or Off. The factory
setting is Off.
Menu 6.4.2 Cooling curve [U]
The selected curve slope (cooling curve) is shown here). The
value is adjustable between 1 and 3. The factory setting is 2.
Menu 6.4.3 Offset cold curve [U]
The selected cooling curve offset is shown here. The value
is adjustable between -10 and +10. The factory setting is 0.
Menu 6.4.4 Start temp. heating [U]
Outdoor temperature (menu 4.0) at the outdoor sensor
(UG) when the heat pump switches to heating mode. The
value is adjustable between 0 and 30 °C. The factory set-
ting is 20 °C.
Menu 6.4.5 Start temp. cooling [U]
Outdoor temperature (menu 4.0) on the outdoor sensor
(UG) when the heat pump switches to cooling mode. The
value is adjustable between 0 and 30 °C. The factory set-
ting is 25 °C.
Menu 6.4.6 Start active cooling [U]
The heat pump starts to actively produce cooling at this
degree-minute surplus. The value is adjustable between 10
and 500 degree-minutes. The factory setting is 30 degree-
minutes.
Menu 6.4.7 GM for compr.-step [U]
Degree-minute difference between compressor stages. The
value is adjustable between 10 and 500 degree-minutes.
The factory setting is 30 degree-minutes.
Menu 6.4.8 Diff Passive/Active [U]
If the flow temperature on the sensor (FG) exceeds the cal-
culated flow temperature + this value the system switches
to active cooling. The value is adjustable between 1 and 9
°C. The factory setting is 4 ° C.
Menu 6.4.9 Min. flow temp. [U]
The lowest flow temperature in cooling mode. The value is
adjustable between 2 and 65 °C. The factory setting is 5
°C.
Menu 6.4.10 Periodtime shunt [U]
The time period for the shunt (SV-K) is chosen here.
Adjustable between 1 and 500 seconds.
The factory setting is 5 °C
Menu 6.4.11 Shunt intensificat. [U]
The amplification for the shunt (SV-K) is chosen here. For
example, a 2 degree difference between the flow line and
the calculated flow line with 5 in amplification gives 10
secs/min controlling the shunt. The value can be set be-
tween 1 and 10. The factory setting is 1.
Menu 6.4.12 Time betw. heat cold [U]
The time the heat pump must wait between production of
heat cooling is set here. The value can be set between 0
and 10 hours. The factory setting is 3 hours.
Menu 6.4.13 Brinepump cont. AC [U]
Here you select if the brine pump (KBP) should run continu-
ously during active cooling. The factory setting is No.
Menu 6.4.14 Return [U]
Pressing the enter button returns you to menu 6.4.0.
Menu 6.5.0 Pool settings [N]
Shows the current pool temperature on the sensor (PTG).
Pressing the enter button takes you to sub-menus for the
Pool settings. Only shown when pool is selected in menu
9.1.5.
Menu 6.5.1 Start temp. pool [U]
Here you select at which pool temperature on the sensor
(PTG) heating should start. The value is adjustable between
5 and 60 °C in increments of 0.5 °C. The factory setting is
22.0 °C.
Menu 6.5.2 Stop temp. pool [U]
Here you select at which pool temperature on the sensor
(PTG) heating should stop. Adjustable between 5 and 60
°C in increments of 0.5 °C. The factory setting is 24.0 °C.
Menu 6.5.3 Periodtime heat/pool [U]
The length of time is set here. The value is adjustable
between 10 and 1000 minutes. The factory setting is 100
minutes.
Menu 6.5.4 Max-Time heatproduct [U]
Here you select how much time of the period time (menu
6.5.3) is to be used to heat the house when there is a need
of heating and pool heating. The value is adjustable be-
tween 0 and 1000 minutes. The factory setting is 50 min-
utes.