If a room sensor is not activated, the desired offset of
the heating curve is set. One step is usually enough to
change the room temperature by one degree, but in
some cases several steps may be required. This setting
applies to all climate systems without room sensors.
Vacation scheduling starts at 00:00 on the start date and
stops at 23:59 on the stop date.
TIP
Stop the holiday setting about a day before
your return so that room temperature and hot
water have time to return to their usual levels.
TIP
Set the vacation setting in advance and activate
just before departure in order to maintain the
comfort.
MENU 4.9 - ADVANCED
Menu advanced has orange text and is intended for
the advanced user. This menu has several sub-menus.
MENU 4.9.1 - OP. PRIORITISATION
op. prioritisation
Setting range: 0 to 180 min
Factory setting: 60 min for hot water, 0 min for others
Choose here how long the heat pump should work with
each requirement if there are two or more requirements
at the same time. If there is only one requirement the
heat pump only works with that requirement.
The indicator marks where in the cycle the heat pump
is.
If 0 minutes is selected, this means that the requirement
is not prioritised, but will only be activated when there
is no other requirement.
MENU 4.9.2 - AUTO MODE SETTING
start cooling (accessory required)
Setting range: -20 40 °C
Factory setting: 25
stop heating
Setting range: -20 40 °C
Default values: 17
stop additional heat
Setting range: -25 40 °C
Factory setting: 5
filtering time
Setting range: 0 48 h
Default value: 24 h
When the operating mode is set to "auto", the heat pump
selects when start and stop of additional heat and heat
production is permitted, dependent on the average
outdoor temperature. If accessories for cooling are
present or if the heat pump has the integrated cooling
function, you can also select the start temperature for
cooling.
Select the average outdoor temperatures in this menu.
Caution
It cannot be set "stop additional heat" higher
than "stop heating".
filtering time: You can also set the time (filtering time)
over which the average temperature is calculated. If you
select 0, the current outdoor temperature is used.
Caution
In systems where heating and cooling share
the same pipes "stop heating" cannot be set
higher than "start cooling" if there is not a
cooling/heating sensor.
29Chapter 3 | Control - MenusNIBE F1345