Control
FIGHTER 1320
68
S
S
S
S
S
S
S
S
S
S
S
N
Menu 5.5.0 Sensor calibration
Sensors are calibrated here using the sub-menus.
All (Menu 5.5.1 - 5.5.9) are adjustable between -5
and +5 °C in increments of 0.1 °C. Factory setting
on all is 0 °C.
Menu 5.5.1 Heating return A
Menu 5.5.2 Heating return B
Menu 5.5.3 Brine in
Menu 5.5.4 Brine out A
Menu 5.5.5 Brine out B
Menu 5.5.6 Outdoor temp.sensor
Menu 5.5.7 Room temp. sensor
Menu 5.5.8 Flow temp. sensor 1
Menu 5.5.9 Flow temp. sensor 2
Menu 5.5.10 Return
Pressing the Enter button returns you to menu
5.5.0.
Menu 5.6 Return
Pressing the Enter button returns you to menu 5.0.
5.0 Heat pump
U
U
U
U
U
U
Menu 5.4.7 Oper.mode heat pump A
The operating mode for the heating medium pump
A (VBP-A) is set here. Selectable options are:
Intermittent:The heating medium pump starts 20
seconds before and stops 20 seconds after the
compressor.
Continuous: Continuous operation.
Economy: The pump is operational a specific time
per period (see menu 6.1.2 and 6.1.3), and togeth-
er with the compressor.
The factory setting is Intermittent.
Menu 5.4.8 Level monitor
Select here if an external brine pressostat, level
sensor or flow sensor is connected to the “EBV
card”.
Can be set to On (NC), On (NO) or Off. The factory
setting is Off.
Menu 5.4.9 Quickstart of compr.
Select Yes in order to reduce the pressure-com-
pensating time to 0 and in doing so permit a quick
start.
NOTE! The setting returns to No as soon as the
heat pump has implemented the action.
Menu 5.4.10 Factory pre-set
The heat pump can be reset to the factory settings
here.
Normal: Factory settings on all settings except the
system settings (menu 0.x and 9.x) and operating
statistics.
Expanded: Factory settings on all settings except
operating statistics.
NOTE! The setting returns to No as soon as the
heat pump has implemented the action.
Menu 5.4.11 Reset alarm
Resetting/acknowledging an alarm on FIGHTER
1320.
Menu 5.4.12 Return
Pressing the enter button returns you to menu
5.4.0.