S735 in incorrect operating mode.
Enter menu 4.1 - "Operating mode". If "Auto" mode is
selected, select a higher value for "Stop heating" in
menu 7.1.10.2 - "Auto mode setting".
If mode "Manual" is selected, select "Heating". If this is
not enough, select "Additional heat".
Too low set value on the automatic heating control.
Adjust via the smart guide or home screen "Heating"
If the room temperature is only low in cold weather, the
curve slope in menu 1.30.1 - "Curve, heating" may need
to be adjusted upwards.
Too low or no operating prioritisation of heat.
Enter menu 7.1.10.1 - "Operating prioritisation" and in-
crease the time for when heating is to be prioritised.
Note that if the time for heating is increased, the time
for hot water production is reduced, which can give a
smaller amount of hot water.
Hot water demand "Large" selected in combination with
large hot water outlet.
When you have selected hot water demand "Large",
S735 prioritises hot water production over heat produc-
tion.
If you want to change hot water mode: Enter menu 2.2
and select "Small" or "Medium".
"Holiday" activated in menu 6 - "Scheduling".
Enter menu 6 and deactivate.
External switch for changing room temperature activated.
Check any external switches.
The heating medium pump (GP1 has stopped.
Air in the climate system.
Vent the climate system.
Closed valves to the climate system
Open the valves.
Incorrect value set in menu 7.1.5.1 - "Int elec add heat".
Enter menu 7.1.5.1 and increase the value on "Max. set
electrical power".
HIGH ROOM TEMPERATURE
Too high set value on the automatic heating control.
Adjust via the smart guide or home screen "Heating"
If the room temperature is only high in cold weather,
the curve slope in menu 1.30.1 - "Curve, heating" may
need to be adjusted downwards.
External switch for changing room temperature activated.
Check any external switches.
LOW SYSTEM PRESSURE
Not enough water in the climate system.
Fill the climate system with water and check for leaks
(see chapter "Filling and venting").
LOW OR A LACK OF VENTILATION
The exhaust air filter (HQ10) is clogged.
Change the filter.
The ventilation is not adjusted.
Order/implement ventilation adjustment.
Exhaust air device blocked or throttled down too much.
Check and clean the exhaust air devices.
Fan speed in reduced mode.
Enter menu 1.2.1 - "Fan speed" and select "Normal"
Scheduling activated.
Enter menu 6 - "Scheduling". Switch off the function or
adjust the settings.
External switch for changing the fan speed activated.
Check any external switches.
HIGH OR DISTRACTING VENTILATION
The exhaust air filter (HQ10) is clogged.
Change the filter.
The ventilation is not adjusted.
Order/implement ventilation adjustment.
Fan speed in forced mode.
Enter menu 1.2.1 - "Fan speed" and select "Normal"
Night cooling activated.
Enter menu 1.2.2 - "Night cooling". Switch off the func-
tion or adjust the settings.
Scheduling activated.
Enter menu 6 - "Scheduling". Switch off the function or
adjust the settings.
External switch for changing the fan speed activated.
Check any external switches.
THE COMPRESSOR DOES NOT START
There is no heating or hot water demand.
S735 does not call on heating or hot water.
The heat pump defrosts.
The compressor starts, when defrosting is complete.
Compressor blocked due to the temperature conditions.
Wait until the temperature is within the product’s work-
ing range.
Minimum time between compressor starts has not been
reached.
Wait for at least 30 minutes and then check if the com-
pressor has started.
63Chapter 11 | Disturbances in comfortNIBE S735