Menu Settings
This menu shows all adjustable parameters in the system.
Some parameters are not relevant for all systems.
Set temp tank1
Maximum temperature in the tank during normal opera-
tion. (Adjustable 15 °C to 90 °C with default setting 65
°C)
dTStart tank1
Temperature difference between collector (T1) and Tank1
(T2) at which the pump starts charging to tank. (Ad-
justable 3 °C to 40 °C with default setting 7 °C)
dTStop tank1
Temperature difference between collector (T1) and Tank1
(T2) at which the pump stops. (Adjustable 2 to (dTSet
tank1 -2 °C) with default setting 3 °C)
&ROOHFWRU
7HPS
7DQN
6SHHG FRQWURO SXPS
7DQN
G76WDUW
G76WDUW
G76WRS
G76WDUW


6HW 7HPS WDQN
PD[ WDQN
WHPSHUDWXUH
Min speed pump
Inställningar ------------------ -- -----
6HWWLQJV
6HW WHPS WDQN
G76WDUW WDQN
G76WRS WDQN
6HW WHPS WDQN
G76WDUW WDQN
G76WRS WDQN
0LQ UHY SXPS
 r&
r&
r&
 r&
r&

To select the row "Min rev pump" press (+) or (-). Then
press
to activate the menu choice.
Minimum speed of the pump is set with (+) and (-) (ad-
justable 50 % to 100 % with default value 100 %).
For speed control using Triac, select PhAC SC.
When dT is below dTMax and the set "Min rev pump" is
used at dTmin the speed of the pump decreases.
Hastighet på pumpar
dTMin
dTMax
100%
Min varvtal pump
dTOmråde / 2
Hastighetsområde / 2
6SHHG UDQJH
3XPS VSHHGV
0LQ VSHHG SXPS
G76WDUW
G75DQJH
G76WRS
NOTE
Speed control is performed through phase control with
Triac. Check before changing min speed:
- that the pump can use this type of speed control.
- the minimum pump speed.
- that the speed selector on the pump is set to maxim-
um speed.
Extra heating
(Thermostat function is only available if extra function "ex-
ternal heat" is selected in menu "Extra".)
T3 start
T3 start +
hysteres
Extra P3
Temperatur i toppen av tank1 T3 (°C)
7HPSHUDWXUH DW WKH WRS RI WKH WDQN 7 r&
7 6WDUW
7
([WUD 3
K\VWHUHVLV
Start
Temperature level at the top of the tank (T3) at which
the thermostat function activates pump (P3) to heat the
top of the tank. (Adjustable 20 °C to 90 °C with default
value 40 °C.)
Hysteresis
Setting hysteresis for final heating of the top of the tank.
(Adjustable 2 °C to 30 °C with default value 10 °C.)
Extra cooling
(Only available if extra function "cooling" is selected in menu
"Extra".)
P3
Temperatur i toppen av tank1 T3 (°C)
Kylning start
Kylning stopp
(start – hysteres)
7HPSHUDWXUH DW WKH WRS RI WKH WDQN 7 r&
&RROLQJ 6WDUW
&RROLQJ 6WRS
VWDUW K\VWHUHVLV
3
Cooling start
Temperature level at the top of the tank (T3) to start
cooling the tank through circulation with extra pump (P3)
to another heating layer.
(Adjustable 20 °C to 90 °C with default value 40 °C.)
Cooling hysteresis
Setting of hysteresis to stop cooling function. Cooling is
stopped when the temperature at the top of the tank
(T3) is below "Cooling start" minus "Hysteresis". (Ad-
justable 1 °C to 30 °C with default value 10 °C.)
11SCU 10
For the Installer
Menu Settings