ENGLISH – 47
Always close (0x87)
– Active (ON
4
OFF, default = OFF)
This function enables the automation to autonomously run a closing manoeuvre after a blackout. The function only activates after a blackout.
Function ON = when the power is restored the closing manoeuvre is carried out.
Function OFF = when the power is restored, the automation remains stationary.
a
WARNING: for safety-related reasons, when the function is active, the closing manoeuvre is preceded by a pre-ash, the
duration of which is programmed through the “stand-by time” function (see below).
– (ALWAYS CLOSE
4
SAVE AUTOMATIC CLOSING, default = ALWAYS CLOSE) mode
The function has 2 operating modes:
– always close = after a blackout, when the power is restored and the time indicated in the “stand-by time” parameter has elapsed, the auto
-
mation runs an automatic closing manoeuvre
– save closing = by activating this mode, when power is restored after a blackout, two results can be obtained:
– execution of the automatic closing manoeuvre according to the time set in the “pre-ashing time” function, if the countdown of this time was
in progress when the blackout occurred;
– execution of the closing manoeuvre if an automatic closing manoeuvre was under way at the time of the blackout and had not been com
-
pleted.
Note – If the automatic closing manoeuvre was cancelled before the blackout (for example, by sending the Stop command), the closing manoeuvre will
not be performed when the power is restored.
– Stand-by time (0
4
20(s), default = 5s)
This parameter can be used to programme in the control unit the desired stand-by time that must elapse between the restart due to a blackout and the
start of a closing manoeuvre. This parameter is only managed if the “ACTIVE” mode is set to ON.
Force management (0x47)
– Opening force (10
4
100 (%), default
k
= 95% -
and
= 60%)
The function can be used to adjust the force applicable by the motor during an opening manoeuvre.
With the “heavy door” setting = the default value is 95%
With the “light door” setting = the default value is 60%
– Open slowdown force (10
4
100 (%), default
k
= 70% -
and
= 40%)
The function can be used to adjust the force applicable by the motor during the slowdown phase of an opening manoeuvre.
With the “heavy door” setting = the default value is 70%
With the “light door” setting = the default value is 40%
– Closing force (10
4
100 (%), default
k
= 95% -
and
= 60%)
The function can be used to adjust the force applicable by the motor during a closing manoeuvre
With the “heavy door” setting = the default value is 80%
With the “light door” setting = the default value is 60%
– Close slowdown force (10
4
100 (%), default
k
= 60% -
and
= 40%)
The function can be used to adjust the force applicable by the motor during the slowdown phase of a closing manoeuvre
With the “heavy door” setting = the default value is 60%
With the “light door” setting = the default value is 40%
– Manual force level (0
4
600, various defaults, 2 x
c
)
This function can be used to adjust the parameters of the force that the motor must apply within the “AMP exclusion position” during the approach to
the ground.
[Board 1] - Force to be applied during the door’s approach to the ground ( 0
4
100 %)
[Board 2] - Maximum intervention time during the door’s approach to the ground ( 0
4
600ms).