Mains
Supply
Max Input
Current (A)
ID300K Ref
Fuse Ratings Cable Size
CEI UL mm
2
AWG
230V
1ph
4.5 12017 6 6
1 16
5.3 12024 6 6
8.1 12030 10 10
9.1 22035 16 15
1.5 12
12 22052 16 15
14.3 22057 16 15
10.2 32075 16 15
12.2 32087 16 15
2.5 1012.2 32120 20 20
14.8 32155 20 20
Mains
Supply
Max Input
Current (A)
ID300K Ref
Fuse Ratings Cable Size
CEI UL mm
2
AWG
460V
3ph
1.6 14012 6 6
1.5 12
2.2 14015 6 6
2.9 14018 6 6
3.4 14021 6 6
3.5 14025 6 6
3.5 14030 6 6
3.9 14033 10 10
7 24042 10 10
7.5 24050 10 10
8 24070 16 15
2.5 109.5 24085 16 15
13 34119 20 20