ID300/302 Integrated Motor Drive | Quick Start Commissioning
5.1.4 Saving Parameters
When changing a parameter in 0 Menu, the new value is saved when pressing Enter to return to
Parameter View Mode from Parameter Edit Mode.
If parameters have been changed in the advanced menus, the change will not be saved automatically.
A Save function must be initiated. Follow the procedure below.
1. Select SAVE in Pr mm.000*.
2. Either press the Red reset keypad button or toggle the reset digital input.
* Where mm can be any menu number.
5.1.5 Restoring Parameter Defaults
Restoring parameter defaults by this method saves the default values in the drive memory. User
security status Pr 00.010isnota󰀨ectedbythisprocedure.
1. Ensure that the drive is not enabled, i.e., the drive is in Inhibit state.
2. Select ‘Reset 50 Hz Defs’ in Pr 00.000.
3. Press the Red reset keypad button.
Note: Motor parameters Pr 00.006 to Pr 00.009 and their relevant advanced parameters (Pr 05.007 to
Pr 05.010)arenota󰀨ectedbythisprocedure.
Some ID300/302 parameters are set at the factory to take in account the characteristics of the
motor,thedrive,andtheoptionsalreadyttedatfactory.Thisavoidsanyextrasettingsforthe
customer. But if drive default parameter values are restored during commissioning, the factory
preset parameters will be lost and set back to their default value (except the ones of the motor
rating). If it is necessary to restore the parameter default values, it is not recommended to set the
parameters to the same values as already done at the factory.
WARNING
!