nilan Compact S Series - Data Logging Configuration; Setting Data Logging Interval

nilan Compact S Series
33 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Subject to alterations Page 27 of 33
Datalog
The datalog interval is set via the menu SERVICE - DATALOG INTV at between 1 and 120
minutes.
If 0 / OFF is selected, logging is not periodical, but only on events and alarms.
Temperatures are logged in Celsius, in whole degrees, in order to minimise the log file size.
The status of digital inputs and outputs is combined in two shared log variables: ”Din” and
”Dout”.
HOTWATER
AIR
QUALITY
AIR
EXCHANGE
DEFROST
INLET
CONTROL
SERVICE
ENTER
TEMP.
CONTROL
PRESET
OFF
ROOM
KONTROL
RESTART
OFF
MANUAL
OFF
INLET
HEATING
Data increment
[1..120] minutes
MODBUS
ADR 30
DATALOG
INTV 10
Figur 22: The "Datalog" Menu