6 Operating status messages
BU 0600 en-2319 189
C004 4.1 Overcurrent measurement
"Overcurrent measurement"
Warning: pulse switch off is active
The limit for activation of pulse switch off (P537) has been
reached (only possible if P112 and P536 are switched off)
• FI is overloaded
• Drive sluggish, insufficiently sized
• Ramps (P102/P103) too steep -> Increase ramp time
• Check motor data (P201 … P209)
• Switch off slip compensation (P212)
C008 8.0 Parameter loss Warning:
One of the cyclically saved messages such
as operating hours or enabling time could
saved successfully.
The warning disappears as soon as saving can be
successfully performed.
C012 12.1 Motor Limit / Customer
"Motor switch-off limit"
Warning: 80 % of the drive switch-off limit (P534 [-01]) has
been exceeded.
• Reduce load on motor
• Set higher value in (P534 [-01]).
12.2 Generator limit
"Generator switch-off limit"
Warning: 80 % of the generator switch-off limit (P534 [-02])
has been reached.
• Reduce load on motor
• Set higher value in (P534 [-02]).
12.5 Load monitor Warning due to overshooting or undershooting of
permissible load torques ((P525) … (P529)) for the time set
in (P528).
• Adjust load.
• Change limit values ((P525) ... (P527)).
• Increase delay time (P528).
Error message for POSICON
instructions BU 0610
C026
• µSD card inserted incorrectly
• µSD card defective