Supplementary Manual DeviceNet for NORDAC SK 200E
60 Subject to technical amendments BU 0280 GB
Parameter
{Factory setting}
Setting value / Description / Note Device Supervisor
Parameter
set
P173 Module status
0 ... FFFF (hex)
{ 0000 }
Possible values:
Bit 0 = Bus status “Online / Not connected”
Bit 1 = Bus status “Online / Connected”
Bit 2 = Timeout (DeviceNet monitoring or time in P151)
Bit 3 = Faulty DIP setting
X1
Bit 4 = DeviceNet
BUS WARNING
Bit 5 = DeviceNet
BUS OFF
Bit 6 = System bus
BUS WARNING
Bit 7 = System bus “BUS OFF” Bit 8 = Status FI1
Bit 9 = Status FI 1
Bit 10= Status FI 2
Bit 11= Status FI 2
Bit 12= Status FI 3
Bit 13= Status FI 3
Bit 14= Status FI 4
Bit 15= Status FI 4
Status for FI x:
Bit High Bit Low Status
0 0 FI is offline
0 1 Unknown FI
1 0 FI is online
1 1 FI lost or switched off
P174 Digital inputs
0 ... 15
{ 0 }
Instantaneous view of input level logic.
Possible values:
Bit 0= Input 1 (DIN1)
Bit 1= Input 2 (DIN2)
Bit 2= Input 3 (DIN3)
Bit 3= Input 4 (DIN4)
P175 Digital outputs
0 ... 3
{ 0 }
Instantaneous view of output level logic.
Possible values:
Bit 1= Output 1 (DO1)
Bit 2= Output 2 (DO2)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Nord Drivesystems SK CU4-DEV and is the answer not in the manual?

Nord Drivesystems SK CU4-DEV Specifications

General IconGeneral
BrandNord Drivesystems
ModelSK CU4-DEV
CategoryDC Drives
LanguageEnglish

Related product manuals