6 Error monitoring and error messages
BU 0280 GB Subject to technical amendments 65
6.2.2 Table of possible error messages in the bus module
The following error messages concern bus-related messages, which are indicated on the DeviceNet module
(SK CU4DEV or SK TU4DEV(-
…)).
Display
in the SimpleBox
Fault
Text in the ParameterBox
Cause
Remedy
Group Details in
P170
E1000
1000 EEPROM error
Module faulty
1010 System bus 24V missing
Check connections and supply cables
Ensure 24V voltage supply
1020 System bus timeout
Check time set in parameter (P151).
Telegram transfer is faulty.
Check external connection.
Check bus protocol program process.
Check Bus master
1030 System bus OFF
Check connections and supply cables
Ensure 24V voltage supply
Check Bus master
5210 DeviceNet Bus OFF
5211 Address already allocated
Avoid double assignment of addresses
Comply with address range 1 ... 63
Match master addressing to option addressing
5212 Illegal baud rate
Invalid setting on DIP switch
5220 DeviceNet Timeout