SK 54xE – Users Manual for Frequency Inverters
150 BU 0505 EN-3021
P546 [-01]
...
[-05]
Digital Bus setpoint
(Function of bus setpoint)
S P
0 ... 57
{ [-01] = 1 }
all other { 0 }
In this parameter, during bus actuation a function is allocated to the setpoint provided.
NOTE:
The setpoints 4 and 5 must be supported by the relevant bus module. For further
details please refer to the manual for the frequency inverter (P400, P546), the
relevant BUS operating instructions or the manuals BU 0510 / BU0550.
[-01] = Bus setpoint 1 [-02] = Bus setpoint 2 [-03] = Bus setpoint 3
[-04] = Bus setpoint 4 [-05] = Bus setpoint 5
Pos: 360 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P500- P599/Parameter P546 – Funk tion Bus-Sollwerte, Einstellungen [SK 5 xxE] @ 2\mod_1354267859195_3 88.docx @ 51897 @ @ 1
Torque current limit (P112)
Set relays, "Output status"
(P434/441/450/455=38)
Set analog output (P418=31)
... 45 reserved from SK 530E and above
BU 0510
(P536)
Setpoint Torque processreg.,
"Setpoint
torque process controller"
reserved from SK 530E and above
BU 0510
Actual PID frequency limited
Motor temperature (SK 540E and above)
Actual PID frequency monitored
reserved from SK 540E and above
BU 0510
(P300)
(SK 540E and
above)
(P214)
(SK 540E and above)
Reserved
(SK 540E and
above)
reserved from SK 540E and above
BU 0510
Process controller actual value
reserved from SK 540E and above
BU 0510
Process controller setpoint
Scaling details: See Section 8.7
Pos: 363 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P500- P599/Parameter P549 – Funk tion Poti-B ox @ 0 \mod_1328098389279_388. docx @ 12008 @ @ 1
P549
Pot Box function
(PotentiometerBox function)
S
0 ... 16
{ 0 }
In this parameter, the setpoint of the PotentiometerBox (SK TU3-
function. (An explanation can be found in the description of P400.)
As of software version 1.7 R0, on setting 4 or 5, the ControlBox or the ParameterBox are also set
to function as suppliers of auxiliary setpoints (see Section 4.5).
0 = Off
1 = Setpoint frequency
2 = Torque current limit
3 = Actual frequency PID
4 = Frequency addition
5 = Frequency subtraction
6 = Current limit
7 = Maximum frequency
8 = Actual PID frequency limited
9 = Actual PID frequency monitored
10 = Servo mode torque
11 = Torque precontrol
12 = Reserved
13 = Multiplication
14 = Process controller actual value
15 = Process controller setpoint
Process controller lead