5.5 Control terminals
BU 0500 GB Subject to technical alterations 101
Parameter Set value / Description / Note Device Supervisor
Parameter
set
P466 Minimum frequency process
controller
P
-400.0 ... 400.0 Hz
[ 0.0 ]
With the aid of the minimum frequency process controller the control ratio can also be kept to a
minimum ratio, even with a master value of “zero”, in order to enable adjustment of the
compensator. Further details in P400 and Section 8.2.
P470 Digital input 7
SK 520E
0 ... 72
[ 0 ]
No function as factory setting, control terminal 27 (DIN7)
Various functions can be programmed. These can be taken from tables for P420…P425.
P475 … - 01
...
... - 09
Switch on/off delay
S
Adjustable switch-on/off delay for the digital inputs and the digital functions of the analog inputs.
Use as a switch-on filter or simple process control is possible.
[01] = Digital input 1
[02] = Digital input 2
[03] = Digital input 3
[04] = Digital input 4
[05] = Digital input 5
[06] = Digital input 6 (only SK 52x/53xE)
[07] = Digital input 7 (only SK 52x/53xE)
[08] = Digital function, analog input 1
[09] = Digital function, analog input 2
-30.000 ... 30.000 s
[ 0.000 ]
Positive values = switch-on delayed Negative values = switch-off delayed
P480 ... - 01
...
... - 12
Function Bus I/O In Bits
S
The Bus I/O In Bits are perceived as digital inputs. They can be set to the same functions
(P420...425).
[01] = Bus I/O In Bit 0
[02] = Bus I/O In Bit 1
[03] = Bus I/O In Bit 2
[04] = Bus I/O In Bit 3
[05] = Bus I/O In Bit 4
[06] = Bus I/O In Bit 5
[07] = Bus I/O In Bit 6
[08] = Bus I/O In Bit 7
[09] = Flag 1
[10] = Flag 2
[11] = Bit 8 BUS control word
[12] = Bit 9 BUS control word
0 ... 72
[ 0 ]
The possible functions for the Bus In Bits can be found in the table of functions for the digital
inputs P420...425.
For further details, please refer to the manual for the AS interface, BU 0090.