Parameter Set value / Description / Note Device Supervisor
Parameter
set
P506
Automatic error
acknowledgement
S
0 ... 7
[ 0 ]
In addition to the manual error acknowledgement, an automatic one can also be selected.
0 = No automatic error acknowledgement
1 ... 5 = Number of permissible automatic malfunction acknowledgments within one mains-
on cycle. After mains off and switch on again, the full amount is again available.
6 = Always, an error message will always be acknowledged automatically if the cause of
the error is no longer present.
7 = ENTER key, acknowledgement is only possible using the ENTER key or by mains
switch-off. No acknowledgement is implemented by removing the enable!
P507 PPO Type
1 ... 4
[ 1 ]
This parameter can only be used with the technology unit Profibus, DeviceNet or InterBus
See also additional descriptions BU 0020, BU 0080, BU 0070
P508 Profibus address
1 ... 126
[ 1 ]
Profibus address, only with the technology unit Profibus
See also the additional description for the Profibus control BU 0020
P509 Control word source
0 ... 10
[ 0 ]
Selection of the interface via which the FI is controlled.
0 = Control terminals or keyboard control ** with the Control Box (when P510=0), the
Parameter Box (not ext. p-box) or via Bus I/O Bits.
1 = Only control terminals *, the FI can only be controlled via the digital and analog input
signals or via the Bus I/O Bits.
2 = USS control word *, the control signals (enable, rotation direction, etc.) are transferred
via the RS485 interface, the setpoint via the analog input or the fixed frequencies.
3 = CAN control word *
4 = Profibus control word *
5 = InterBus control word *
6 = CANopen control word *
7 = DeviceNet control word *
8 = reserved
9 = CAN Broadcast *
10 = CANopen Broadcast *
*) Keyboard control (ControlBox, ParameterBox) is blocked, parameterisation is still possible.
**) If the communication during keyboard control is interrupted (time out 0.5 sec),
the FI will block without an error message.
NOTE:
For details about the respective Bus systems please
refer to the respective Options descriptions:
BU 0020 = Profibus BU 0050 = USS
BU 0060 = CAN/CANopen BU 0070 = InterBus
BU 0080 = DeviceNet BU 0090 = AS Interface