6 Error messages
BU 0500 GB Subject to technical alterations 131
Display
in the ControlBox
Group Detail in
P700 / P701
Error
text in the Parameter Box
Cause
Remedy
E011
11.0 Customer unit
(AnalogDigital converter error)
Internal customer unit (internal databus) faulty or damaged by
radio radiation (EMC)
Check control terminals connection for short-circuit.
Minimize EMC interference by laying control and power
cables separately.
Earth the devices and shields well.
E012
12.0 Watchdog customer /
customer error
The Watchdog function is selected at a digital input and the
impulse at the corresponding digital input is not present for
longer than the time set in parameter P460 >Watchdog time<.
12.1 Drive switch-off limit
exceeded
The drive switch-off limit P534 [01] has triggered.
Reduce load on motor
Set a higher value in P534 [01].
12.2 Generator switch-off value
exceeded
The generator switch-off limit P534 [02] has triggered.
Reduce load on motor
Set a higher value in P534 [02].
13.0 Encoder error
No signal from encoder
Check 5V sensor if available.
Check supply voltage of encoder.
13.1 Speed slip error
The slip speed error limit was reached.
Increase setting in P327.
E013
13.2 Slip error switch-off
monitoring
The slip error monitoring was triggered; the motor could not
follow the setpoint.
Check motor data P201-P209! This data is very
important for the current control
Check motor circuit.
If necessary, check the encoder setting P3xx in
Servo mode.
Increase setting value for torque limit in P112.
Increase setting value for current limit in P536.
16.0 Motor phase error
A motor phase is not connected.
Check P539
Check motor connections
E016
16.1 Motor current monitoring for
braking mode
Required exciting current not achieved at moment of switch-
on.
Check P539
Check motor connections
E018
18.0 Safety circuit
The safe pulse block was triggered while the frequency
inverter was being enabled.
Only available in SK 510E and SK 530E. Details in
manual BU 0530 (www.nord.com
).