8 Additional information
BU 0500 GB Subject to technical alterations 149
Cable emissions 150kHz - 30 MHz
Device type
Max. motor cable, shielded
Jumper position
See Section
2.8.6 - 2.8.7
Class A 1 Class B 1
2 - 1 20m 5m
SK 5xxE-250-323-A … SK 5xxE-401-323-A
2 - 2 5m -
2 - 1 20m 5m
SK 5xxE-550-340-A … SK 5xxE-751-340-A
2 - 2 5m -
Overview of the standards, which according to product standard EN 61800-3 are applicable as testing and
measuring methods for electric drives whose speed can be altered:
Interference emission
A 1
Emission from cables
(interference voltage)
EN 55011
B 1
A 1
Radiated emissions
(Interference field strength)
EN 55011
-
Interference immunity EN 61000-6-1, EN 61000-6-2
ESD, discharge of static electricity EN 61000-4-2 6kV (CD), 8kV (AD)
EMF, high frequency electro-magnetic
fields
EN 61000-4-3 10V/m; 80 - 1000MHz
Burst on control cables EN 61000-4-4 1kV
Burst on mains and motor cables EN 61000-4-4 2kV
Surge (phase-phase / phase-ground) EN 61000-4-5 1kV / 2kV
Cable-led interference due to high
frequency fields
EN 61000-4-6 10V, 0.15 - 80MHz
Voltage fluctuations and drops EN 61000-2-1 +10%, -15%; 90%
Voltage asymmetries and frequency
changes
EN 61000-2-4 3%; 2%
Wiring recommendations
M
3 ~
PE
1
W
V
U
W
V
U
200-240V
or
380-480V
50-60Hz
L
1
L
PE
L
2
/N
L
L
PE
B-B+
SK 5xxE
Shield a ngle
Bra king resist or
(Accessories)