5.5 Control terminals
BU 0500 GB Subject to technical alterations 93
Parameter Set value / Description / Note Device Supervisor
Parameter
set
P420 Digital input 1
0 ... 72
[ 1 ]
Enable right as factory setting, control terminal 21 (DIN1)
Various functions can be programmed. These can be seen in the following table.
P421 Digital input 2
0 ... 72
[ 2 ]
Enable left as factory setting, control terminal 22 (DIN2)
Various functions can be programmed. These can be seen in the following table.
P422 Digital input 3
0 ... 72
[ 8 ]
Parameter set switching Bit 0 as factory setting, control terminal 23 (DIN3)
Various functions can be programmed. These can be seen in the following table.
P423 Digital input 4
0 ... 72
[ 4 ]
Fixed frequency 1 (P429) as factory setting, control terminal 24 (DIN4)
Various functions can be programmed. These can be taken from the following table.
P424 Digital input 5
0 ... 72
[ 0 ]
No function as factory setting, control terminal 25 (DIN5)
Various functions can be programmed. These can be seen in the following table.
P425 Digital input 6
SK 520E
and above
0 ... 72
[ 0 ]
No function as factory setting, control terminal 26 (DIN6)
Various functions can be programmed. These can be seen in the following table.
Digital input 7 function = P470 (only SK 520/530E), control terminal 27 (DIN7)
... Function descriptions follow on the next pages.